SIMATIC S7-1200
Communication
CM 1241 communication module
4/96
Siemens ST 70 · 2011
■
Overview
• For quick, high-performance serial data exchange via point-
to-point connection
• Implemented protocols: ASCII, USS drive protocol,
Modbus RTU
• Additional protocols can also be loaded
• Simple parameterization with STEP 7 Basic
■
Technical specifications
6ES7 241-1CH30-0XB0 6ES7 241-1AH30-0XB0
Product type designation CM 1241 RS485 CM 1241 RS232
Current consumption
Current consumption, max. 220 mA; from L5+; logic 220 mA; from L5+; logic
Power losses
Power loss, typ. 1.1 W 1.1 W
Interfaces
Number of interfaces 1 1
Interface physics, RS 232C (V.24) Yes
Interface physics, RS 422/RS 485 (X.27)
Yes
Point-to-point
Cable length, max. 1000m 10 m
Integrated protocol driver
•ASCII Yes; available as library function Yes
•USS Yes; available as library function
Climatic and mechanical conditions for
storage and transport
Climatic conditions for storage and transport
•Free fall
- Drop height, max. (in packaging) 0.3 m; Five times, in dispatch package 0.3 m; Five times, in dispatch package
•Temperature
- Permissible temperature range -40 °C to +70 °C -40 °C to +70 °C
• Air pressure acc. to IEC 60068-2-13
- Permissible air pressure 1080 to 660 hPa 1080 to 660 hPa
• Relative humidity
- Permissible range (without condensation) at
25 °C
95% 95%
Mechanical and climatic conditions during
operation
Climatic conditions in operation
•Temperature
- Permissible temperature range 0°C to 55°C horizontal mounting
0° C to 45° C vertical mounting
0°C to 55°C horizontal mounting
0° C to 45° C vertical mounting
- Permissible temperature change
5°C to 55°C, 3°C / minute 5°C to 55°C, 3°C / minute
• Air pressure acc. to IEC 60068-2-13
- Permissible air pressure 1080 to 795 hPa 1080 to 795 hPa
© Siemens AG 2011
© Siemens AG 2011