Technical specifications (continued)
6AV6 647-0AE11-3AX0 6AV6 647-0AF11-3AX0 6AV6 647-0AG11-3AX0
Product type designation SIMATIC HMI KTP1000 Basic
color DP
SIMATIC HMI KTP1000 Basic
color PN
SIMATIC HMI TP1500 Basic
color PN
Supply voltage
Supply voltage 24 V DC 24 V DC 24 V DC
Permissible range +19.2 V to +28.8 V DC +19.2 V to +28.8 V DC +19.2 V to +28.8 V DC
Rated current 0.6 A 0.6 A 0.8 A
Memory
Type Flash / RAM Flash / RAM Flash / RAM
Usable memory for user data
1024 kbyte usable memory for
user data
1024 kbyte usable memory for
user data
1024 kbyte usable memory for
user data
Protocols
Protocols (terminal link)
• Sm@rtAccess No No No
Configuration
Configuration tool WinCC flexible Compact
Version 2008 or higher
(to be ordered separately)
WinCC flexible Compact
Version2008orhigher
(to be ordered separately)
WinCC flexible Compact
Version 2008 or higher
(tobeorderedseparately)
Display
Display type TFT, 256 colors TFT, 256 colors TFT, 256 colors
Size 10.4" (211.2 mm x 158.4 mm) 10.4" (211.2 mm x 158.4 mm) 15" (304.1 mm x 228.1 mm)
Resolution (WxH in pixel) 640 x 480 640 x 480 1024 x 768
Backlighting
• MTBF backlighting (at 25 °C) about 50,000 hours about 50,000 hours about 50,000 hours
Operating mode
Control elements Membrane keyboard Membrane keyboard Touch screen
Function keys, programmable
8 function keys 8 function keys None
Connection for mouse/keyboard/
barcode reader
-/-/- -/-/- -/-/-
Touch operation
• Touch screen analog, resistive analog, resistive analog, resistive
• Numeric/alphabetical input Yes (on-screen keyboard) / Yes
(on-screen keyboard)
Yes (on-screen keyboard) / Yes
(on-screen keyboard)
Yes (on-screen keyboard) / Yes
(on-screen keyboard)
Ambient conditions
Mounting position vertical vertical vertical
Maximum permissible angle of
inclination without external venti-
lation
+/- 35 ° +/- 35 ° +/- 35 °
Max. relative humidity 90 % 90 % 90 %
Temperature
• Operation (vertical installation) 0 °C to +50 °C 0°Cto+50°C 0°Cto+50°C
• Operation (max. tilt angle) 0 °C to +40 °C 0°Cto+40°C 0°Cto+40°C
• Transport, storage -20 °C to +60 °C -20°Cto+60°C -20°Cto+60°C
Degree of protection
Front IP65, NEMA 4, NEMA 4x,
NEMA 12 (when installed)
IP65,NEMA4,NEMA4x,
NEMA 12 (when installed)
IP65,NEMA4,NEMA4x,
NEMA 12 (when installed)
Rear IP20 IP20 IP20
© Siemens AG 2011