Overview
• Unmanaged switch for connecting a SIMATIC S7-1200 to an
Industrial Ethernet network with a line, tree or star topology
• Multiplication of Ethernet interfaces on a SIMATIC S7-1200 for
additional connection of up to three programming devices,
operator controls, and further Ethernet nodes
• Simple, space-saving mounting on the SIMATIC S7-1200
mounting rail
• Low-cost solution for implementing small, local Ethernet
networks
• Connection without any problems using RJ45 standard
connectors
• Simple and fast status display via LEDs on the device
• Integral autocrossover function permits use of uncrossed
connecting cables
■
Technical specifications
Order number 6GK7 277-1AA00-0AA0
Product type designation CSM 1277
Data transmission rate
Transmission rate 1 10 Mbit/s
Transmission rate 2 100 Mbit/s
Interfaces
Maximum number of electrical/
optical connections for network
components or terminal equipment
4
Number of electrical connections
• For network components or
terminal equipment
4
• For signal contact
-
• For power supply 1
Design of electrical connection
• For network components or
terminal equipment
RJ45 port
• For signal contact -
• For power supply 3-pin terminal block
Supply voltage, current
consumption, power loss
Type of power supply DC
Supply voltage, external 24 V
• Minimum 19.2 V
•Maximum 28.8 V
Current consumption, maximum
0.07 A
Product component: fusing of
power supply input
Yes
Type of fusing of power supply input
0.5 A / 60 V
Effective power loss at 24 V with DC 1.6 W
Permitted ambient conditions
Ambient temperature
• During operating phase 0…60 °C
• During storage -40 … +70 °C
• During transport -40 … +70 °C
Relative humidity at 25 °C without
condensation during operating
phase, maximum
95 %
IP degree of protection IP20
Design, dimensions and weights
Type of construction SIMATIC S7-1200 device design
Width 45 mm
Height 100 mm
Depth 75 mm
Net weight 0.15 kg
Type of mounting
• 35 mm DIN rail mounting Yes
• Wall mounting
Yes
• S7-300 rail mounting No
© Siemens AG 2011