SIMATIC S7-1200
Central processing units
CPU 1211C
4/9
Siemens ST 70 · 2011
Technical specifications (continued)
4
Galvanic isolation
Galvanic isolation digital inputs
• Galvanic isolation digital inputs No No No
• Between the channels, in groups of 1 1 1
Galvanic isolation digital outputs
• Galvanic isolation digital outputs Yes; Relays Relays Yes
• Between the channels No No No
• Between the channels, in groups of 1 1 1
Permissible potential difference
Between different circuits 500 V DC between 24 V DC and
5VDC
500 V DC between 24 V DC and
5VDC
500 V DC between 24 V DC and
5VDC
EMC
Interference immunity against discharge
of static electricity
• Interference immunity against
discharge of static electricity acc. to
IEC 61000-4-2
Yes Yes Yes
- Test voltage at air discharge 8kV 8kV 8kV
- Test voltage at contact discharge 6kV 6kV 6kV
Interference immunity to cable-borne
interference
• on the supply lines acc. to
IEC 61000-4-4
Yes Yes Yes
• Interference immunity on signal lines
acc. to IEC 61000-4-4
Yes Yes Yes
Surge immunity
• on the supply lines acc. to
IEC 61000-4-5
Yes Yes Yes
Immunity against conducted interference
induced by high-frequency fields
• Interference immunity against
high-frequency radiation acc. to
IEC 61000-4-6
Yes Yes Yes
Emission of radio interference acc. to
EN 55 011
• Emission of radio interferences acc. to
EN 55 011 (limit value class A)
Yes; Group 1 Yes; Group 1 Yes; Group 1
• Emission of radio interference acc. to
EN 55 011 (limit value class B)
Yes Yes Yes
Climatic and mechanical conditions
for storage and transport
Climatic conditions for storage and
transport
•Free fall
- Drop height, max. (in packaging) 0.3 m; five times, in dispatch
package
0.3 m; five times, in dispatch
package
0.3 m; five times, in dispatch
package
•Temperature
- Permissible temperature range -40 °C to +70 °C -40 °C to +70 °C -40 °C to +70 °C
• Relative humidity
- Permissible range
(without condensation) at 25 °C
95% 95% 95%
6ES7 211-1BD30-0XB0 6ES7 211-1HD30-0XB0 6ES7 211-1AD30-0XB0