Technical specifications (continued)
4
Current input
• permissible input current for current input
(destruction limit), max.
40 mA 40 mA
Temperature compensation
• Temperature compensation parameterizable No No
Analog outputs
Number of analog outputs 0 0
Analog value creation
Integrations and conversion time/ resolution per
channel
• Resolution with overrange (bit including sign),
max.
12 bit; + sign 12 bit; + sign
• Integration time, parameterizable Yes Yes
• Interference voltage suppression for
interference frequency f1 in Hz
40 dB, DC to 60 V for interference frequency
50 / 60 Hz
40 dB, DC to 60 V for interference frequency
50 / 60 Hz
Smoothing of measured values
• Parameterizable Yes Yes
• Step: None
Yes Yes
• Step: Low Yes Yes
• Step: Medium Yes Yes
• Step: High Yes Yes
Errors/accuracies
Temperature error (relative to input area) 25°C ±0.1% to 55°C ±0.2% total measurement
range
25°C ±0.1% to 55°C ±0.2% total measurement
range
Basic error limit (operational limit at 25 °C)
• Voltage, relative to input area +/- 0.1 % +/- 0.1 %
• Current, relative to input area +/- 0.1 % +/- 0.1 %
Interference voltage suppression for
f = n x (fl +/- 1%), fl = interference frequency
• Common mode voltage, max. 12 V 12 V
Alarms/diagnostics/status information
Alarms
•Alarms Yes Yes
• Diagnostic alarm Yes Yes
Diagnostics
• Diagnostic functions Yes Yes
• Monitoring the supply voltage to the electronics Yes Yes
•Wire break No No
Diagnostic indication LED
• for status of the inputs Yes Yes
• for maintenance
Yes Yes
Galvanic isolation
Galvanic isolation analog outputs
• between the channels and the power supply of
the electronics
No No
Climatic and mechanical conditions for
storage and transport
Climatic conditions for storage and transport
•Free fall
- Drop height, max. (in packaging) 0.3 m; five times, in dispatch package 0.3 m; five times, in dispatch package
•Temperature
- Permissible temperature range -40 °C to +70 °C -40 °C to +70 °C
• Air pressure acc. to IEC 60068-2-13
- Permissible air pressure 1080 to 660 hPa 1080 to 660 hPa
• Relative humidity
- Permissible range (without condensation) at
25 °C
95% 95%
6ES7 231-4HD30-0XB0 6ES7 231-4HF30-0XB0