SIMATIC S7-1200
Analog modules
SM 1231 analog input module
4/68
Siemens ST 70 · 2011
4
Overview
Analog inputs for SIMATIC S7-1200
With extremely short conversion times
For connecting analog sensors without additional amplifiers
For solving even more complex automation tasks
Technical specifications
6ES7 231-4HD30-0XB0 6ES7 231-4HF30-0XB0
Product type designation SM 1231 AI 4x13 bit SM 1231 AI 8 x 13 bit
Supply voltages
Rated value
•24 V DC Yes Yes
Current consumption
Current consumption, typ. 45 mA 45 mA
from backplane bus 5 V DC, typ. 80 mA 90 mA
Power losses
Power loss, typ. 1.5 W 1.5 W
Connection method
required front connector Yes Yes
Analog inputs
Number of analog inputs 4; current or voltage differential inputs 8; current or voltage differential inputs
Permissible input frequency for current input
(destruction limit), max.
± 35 V ± 35 V
Permissible input current for voltage input
(destruction limit), max.
40 mA 40 mA
Cycle time (all channels) max. 625 μs 625 μs
Input ranges
•Voltage Yes; ±10 V, ±5 V, ±2.5 V Yes; ±10 V, ±5 V, ±2.5 V
• Current
Yes; 0 to 20 mA Yes; 0 to 20 mA
• Thermocouple No No
• Resistance thermometer No No
• Resistance No No
Input ranges (rated values), voltages
• -10 V to +10 V Yes Yes
• Input resistance (-10 V to +10 V) 9 MOhm 9 MOhm
• -2.5 V to +2.5 V
Yes Yes
• Input resistance (-2.5 V to +2.5 V) 9 MOhm 9 MOhm
• -5 V to +5 V Yes Yes
• Input resistance (-5 V to +5 V) 9 MOhm 9 MOhm
Input ranges (rated values), currents
• 0 to 20 mA Yes Yes
• Input resistance (0 to 20 mA)
250 Ohm 250 Ohm
Voltage input
• permissible input voltage for voltage input
(destruction limit), max.
35 V 35 V
© Siemens AG 2011