SIMATIC S7-1200
SIPLUS communication
SIPLUS CM 1241 communication module
4/109
Siemens ST 70 · 2011
4
■
Overview
• For fast, high-performance serial data exchange via point-to-
point coupling
• Implemented protocols: ASCII, USS drive protocol, Modbus
RTU
• Additional protocols can also be loaded
• Simple parameterization with STEP 7 Basic
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific infor-
mation was added.
1)
ISA-S71.04 severity level GX: Long-term load: SO
2
< 4.8 ppm;
H
2
S <9.9ppm; Cl <0.2ppm; HCl <0.66ppm; HF <0.12ppm;
NH < 49 ppm; O
3
< 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d): SO
2
<17.8ppm; H
2
S <49.7ppm;
Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm;
O
3
<1.0ppm; NOX <10.4ppm
2)
The supplied plug covers must remain in place over the unused
interface when operated in atmospheres containing corrosive gases!
The technical documentation on SIPLUS can be found here:
www.siemens.com/siplus-extreme
■
Ordering data
Order No.
H: Subject to export regulations AL: 9I999 and ECCN: EAR99H
I: Subject to export regulations AL: N and ECCN: EAR99H
SIPLUS CM 1241
Order number 6AG1 241-1AH30-
2XB0
6AG1 241-1AH30-
4XB0
Order No. based on
6ES7 241-1AH30-0XB0
Ambient temperature range
-25 ... +70 °C 0 ... +55 °C
Conformal coating
Coating of the printed circuit boards and
the electronic components
Technical data
The technical data of the standard
product applies except for the ambient
conditions.
SIPLUS CM 1241
Order number 6AG1 241-1CH30-
2XB0
6AG1 241-1CH30-
4XB0
Order No. based on 6ES7 241-1CH30-0XB0
Ambient temperature range -25 ... +70 °C 0 ... +55 °C
Conformal coating Coating of the printed circuit boards and
the electronic components
Technical data The technical data of the standard
product applies except for the ambient
conditions.
Ambient conditions
Relative humidity
5 ... 100 %
Condensation permissible
Biologically active substances Conformity with EN 60721-3-3,
Class 3B2 mold and fungal
spores (except fauna)
Chemically active substances
Conformity with EN 60721-3-3,
Class 3C4 incl. salt mist and
ISA–S71.04 severity level G1; G2;
G3; GX
1) 2)
Mechanically active substances Conformity with EN 60721-3-3,
Class 3S4 including conductive
sand, dust
2)
Air pressure (depending on the
highest positive temperature range
specified)
1080 ... 795 hPa
(-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa
(+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa
(+3500 ... +5000 m)
derating 20 K
SIPLUS CM 1241
communication module
(extended temperature range and
medial exposure)
Ambient temperature
25 ... +70° C
Communication module for point-
to-point connection, with one
RS485 interface
I
6AG1 241-1CH30-2XB0
Communication module for point-
to-point connection, with one
RS232 interface
I
6AG1 241-1AH30-2XB0
Suitable for areas with extra-
ordinary medial exposure
(conformal coating)
Communication module for point-
to-point connection, with one
RS485 interface
H
6AG1 241-1CH30-4XB0
Communication module for point-
to-point connection, with one
RS232 interface
H
6AG1 241-1AH30-4XB0
Accessories
See SIMATIC S7-1200 CM 1241
communication module,
page 4/97