SIMATIC S7-1200
Analog modules
SM 1231 thermocouple module
4/81
Siemens ST 70 · 2011
4
Overview
For the convenient recording of temperatures with great
accuracy
7 common thermocouple types can be used
Also for the measurement of analog signals with a low level
(±80 mV)
Can easily be retrofitted to existing plant
Technical specifications
6ES7 231-5QD30-0XB0 6ES7 231-5QF30-0XB0
Product type designation SM1231 TC 4x16 bit SM 1231 TC 8x16 bit
Supply voltages
Rated value
•24 V DC Yes Yes
Current consumption
Current consumption, typ. 40 mA
From backplane bus 5 V DC, typ. 80 mA 80 mA
Power losses
Power loss, typ. 1.5 W 1.5 W
Connection method
Required front connector Yes Yes
Analog inputs
Number of analog inputs 4; Thermocouples 8; Thermocouples
Permissible input frequency for current input
(destruction limit), max.
± 35 V ± 35 V
Technical unit for temperature measurement
adjustable
Degrees Celsius/degrees Fahrenheit Degrees Celsius/degrees Fahrenheit
Input ranges
• Thermocouple Yes; J, K, T, E, R, S, N, C, TXK/XK(L);
voltage range: +/-80 mV
Yes; J, K, T, E, R, S, N, C, TXK/XK(L);
voltage range: +/-80 mV
Input ranges (rated values), voltages
• -80 mV to +80 mV Yes Yes
• Input resistance (-80 mV to +80 mV) >=1MOhm >=1MOhm
Input ranges (rated values), thermoelements
• Type C Yes Yes
• Type E Yes Yes
• Type J Yes Yes
• Type K
Yes Yes
• Type N
Yes Yes
• Type R Yes Yes
• Type S Yes Yes
• Type T Yes Yes
• Type TXK/TXK(L) to GOST Yes Yes
Thermocouple (TC)
• permissible input voltage for voltage input
(destruction limit), max.
+-35V +-35V
Temperature compensation
• Temperature compensation parameterizable No No