SIMATIC S7-1200
Power supplies
SIMATIC S7-1200 PM 1207
4/111
Siemens ST 70 · 2011
■
Technical specifications (continued)
4
1)
SIPLUS module 6AG1 332-1SH71-7AA0 for extended temperature
range -25 °C to +70 °C, derating from +55 °C to +70 °C to 1.5 A
output current. Suitable for use under medial load (e.g. sulfur chloride
atmosphere).
Safety
Primary/secondary isolation Yes, safety extra low output
voltage according to
EN 60950-1 and EN 50178
Protection class Class I
Leakage current <3.5 mA
Safety test
Yes
CE marking Yes
UL/cUL (CSA) approval cULus-listed (UL 508,
CSA C22.2 No. 107.1)
File E197259;
cULus-recognized (UL 60950-1,
CSA C22.2 No. 60950-1),
File E151273
Protection against explosion ATEX (available soon)
FM approval -
Marine approval GL, ABS, DNV, NK
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation Not applicable
Noise immunity EN 61000-6-2
Operating data
Ambient temperature range 0 ... +60 °C with natural
convection
Transport and storage temperature
range
-40 ... +85°C
Humidity class Climate class 3K3 according to
EN 60721, no condensation
Mechanics
Connections
• Supply input L, N, PE One screw-type terminal each for
0.5 ... 2.5 mm
2
• Output + 2 screw-type terminals each for
0.5 ... 2.5 mm
2
•Output - 2 screw-type terminals each for
0.5 ... 2.5 mm
2
Dimensions (W x H x D) in mm 70 x 100 x 75
Weight, approx. 0.3 kg
Mounting Can be snapped onto standard
mounting rail EN 60715 DC
35x7.5/15, wall mounting
Power supply, type 2.5 A
Order number 6EP1 332-1SH71
1)
■
Ordering data
Order No.
L: Subject to export regulations AL: 9I999 and ECCN: N
■
Further information
The perfectly matched, complete SITOP range includes different
switch mode power supply series in addition to a unique range
of add-on modules, which can be used to additionally protect
the 24 V power supply against faults on the primary and
secondary side - all the way to complete protection:
• Redundancy module for setting up a redundant power supply
• Uninterruptible 24 V power supplies with batteries or mainte-
nance-free capacitors for continued operation in the event of
a power failure
• Selectivity modules for the electronic protection of 24 V
feeders against overload and short circuits
More information can be found in the KT 10.1 Catalog and in the
Internet at
www.siemens.com/sitop
SIMATIC S7-1200 PM 1207 6EP1 332-1SH71
Input 120/230 V AC,
output 24 V DC/2.5 A
SIMATIC S7-1200 PM 1207
L
6AG1 332-1SH71-7AA0
(Extended temperature range and
medial exposure, -25 ... +70°C)
© Siemens AG 2011
© Siemens AG 2011
Commenti su questo manuale