Web Interface Pages
30
NXB-CCG NetLinx® Clear Connect™ Gateway
Integration
The NXB-CCG supports a subset of the Lutron Integration Protocol (available on the Lutron website) that is
relevant for the devices that are supported by the NXB-CCG. The NXB-CCG also provides the ability to
download an XML file that provides integration information about the system that is currently programmed to
it (in the Lutron XML format).
Supported Protocol
XML Integration File
The XML file can be downloaded from the web port of the NXB-CCG (80) and asking for the “xml” page
(FIG. 36). If this is done via a browser, you must either already be logged into the NXB-CCG login page or
you will be prompted to login. The credentials can also be added to the web address to automate this process
(“IP-Address-Of-CCT/xml?login=<username>&password=<password>”).
Supported Integration Commands
1) ‘#OUTPUT,<integration ID>,1,<level>’ (goto level)
2) ‘#OUTPUT,<integration ID>,1,<level>,<fade time>’ (goto level with fade)
3) ‘#OUTPUT,<integration ID>,2’ (raise)
4) ‘#OUTPUT,<integration ID>,3’ (lower)
5) ‘#OUTPUT,<integration ID>,4’ (stop)
6) ‘?OUTPUT,<integration ID>,1’ (query level)
7) ‘#DEVICE,<integration ID>,<component number>,3’ (button press)
8) ‘#DEVICE,<integration ID>,<component number>,4’ (button release)
9) ‘#DEVICE,<integration ID>,<component number>,9,1’ (set led on)
NOTE: you cannot set the state of programmed keypad LEDs.
10) ‘#DEVICE,<integration ID>,<component number>,9,0’ (set led off)
NOTE: you cannot set the state of programmed keypad LEDs.
11) ?DEVICE,<integration ID>,<component number>,9 (query led state)
12) ?GROUP,<integration ID>,3 (query occupancy group state)
Supported Monitoring Responses
1) ‘~OUTPUT,<integration ID>,1,<level>’ (dimmer level reporting)
2) ‘~DEVICE,<integration ID>,2,3’ (occ sensor occupied, component always 2)
3) ‘~DEVICE,<integration ID>,2,4’ (occ sensor unoccupied, component always 2)
4) ‘~GROUP,<integration ID>,3,3’ (occ group occupied, component always 3)
5) ‘~GROUP,<integration ID>,3,4’ (occ group unoccupied, component always 3)
6) ‘~DEVICE,<integration ID>,<component number>,3’ (button pressed)
7) ‘~DEVICE,<integration ID>,<component number>,4’ (button released)
8) ‘~DEVICE,<integration ID>,<component number>,9,<state>’ (led state 1/0)
Vedere la pagina 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 40

Commenti su questo manuale

Nessun commento

Vista Caméras de sécurité manuels d'utilisation

La liste de Vista Caméras de sécurité produits contient 6 manuels d'utilisation pour les modèles 4. Tous les guides d'utilisation en format pdf peuvent être téléchargés ou consultés en ligne.

Cliquez sur un alphabet ci-dessous pour faire défiler la liste complète des modèles commençant par cette lettre

Modèles Type de document
Series 3 CCD Cameras
Manuel de l'utilisateur       Vista Series 3 CCD Cameras User's Manual, 52 pages
VBC-800NI30-WC
Manuel de l'utilisateur   Vista VBC-800NI30-WC User's Manual, 1 pages
VIP Kit2 VK2-ENCODER
Manuel de l'utilisateur   Vista VIP Kit2 VK2-ENCODER User manual, 72 pages
Manuel de l'utilisateur   Vista VIP Kit2 VK2-ENCODER User manual, 104 pages
Manuel de l'utilisateur   Vista VIP Kit2 VK2-ENCODER User manual, 68 pages
VPC9030
Manuel de l'utilisateur   Vista VPC9030 User's Manual, 12 pages