150972 iContentSection 1Introduction ...
Before You Begin Installing150972 3-73.6.2 Current Draw WorksheetUse the worksheet beginning on the next page to determine current requirements during
Before You Begin Installing150972 3-93.7 Installation Tasks OverviewThis section of the manual is a chart listing tasks that need to be performed when
Before You Begin Installing150972 3-11Addressable relay modulesAssign addressable relay modules to output groups through programming. (JumpStart assig
150972 4-1Section 4Control Panel Installation4.1 Mounting the 5820 CabinetRead the environmental specifications in Section 3.2 before mounting the 582
Control Panel Installation150972 4-34.3 Battery ConnectionThe 5820 battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same AH rating.
Control Panel Installation150972 4-53. Run extended battery cable from 5820 cabinet through conduit to AB-33 cabinet. See Figure 4-5.Figure 4-5 Batte
Control Panel Installation150972 4-7These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regard
Control Panel Installation150972 4-94.4.2 Wiring ConfigurationsFigure 4-7 illustrates Class A wiring configuration and Figure 4-8 illustrates Class B
Control Panel Installation150972 4-114.5.1 Mounting the 5860This section of the manual describes mounting the remote annunciator. The annunciator can
Control Panel Installation150972 4-13Flush Mounting with an Electrical BoxThe 5860 annunciator can be used with the following types of electrical boxe
Content150972 iiiSection 5SLC Device Installation ...
Control Panel Installation150972 4-154.5.2 5860 Connection to the PanelConnect the 5860 to the panel as shown in Figure 4-14.Figure 4-14 5860 Connect
Control Panel Installation150972 4-174.6.1 5815 Connection to the PanelConnect the 5815 to the IntelliKnight 5820 panel as shown in Figure 4-16. After
Control Panel Installation150972 4-19Figure 4-18 Printer Connection4.7.1 Selecting 5824 OptionsConfiguring the 5824 includes the following steps:• Ad
Control Panel Installation150972 4-214.8 5880 LED Driver ModuleThe 5880 is an LED driver board that can be used in a wide variety of applications, inc
Control Panel Installation150972 4-234.8.3 LED WiringThere are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power f
Control Panel Installation150972 4-254.9 5865-3 / 5865-4 LED Annunciator InstallationThe 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 map
Control Panel Installation150972 4-274.9.2 5865 MountingMount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang el
Control Panel Installation150972 4-294.11 Telephone ConnectionConnect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is availa
Control Panel Installation150972 4-314.12.1.2 Class A Notification WiringYou must use an appliance from the list of compatible appliances in the Appen
Control Panel Installation150972 4-334.12.2.2 Class A InputsYou can connect conventional Class A switches, such as waterflow switches and pull station
Content150972 v7.5.1.2 Auto Test Time ...
Control Panel Installation150972 4-352-Wire Class A Smoke Detector InstallationTo install a Class A two-wire smoke detector, wire as shown in Figure 4
Control Panel Installation150972 4-37Installing 4-Wire Class A Smoke DetectorsFigure 4-37 illustrates how to install 4-wire Class A detectors.Conventi
Control Panel Installation150972 4-394.13.2 Constant PowerUse constant power for applications that require a constant auxiliary power source. Power is
Control Panel Installation150972 4-414.15 Keltron Model 3158 InstallationThe IntelliKnight 5820 is compatible with Keltron Model 3158, used for direct
Control Panel Installation150972 4-434.16 Model 5220 Direct Connect ModuleThe 5220 Direct Connect Module can be used with the 5820 to meet NFPA 72 sta
Control Panel Installation150972 4-454.16.3 NFPA 72 Polarity ReversalWhen the 5220 is wired and programmed for polarity reversal, it reports alarm and
150972 5-1Section 5SLC Device Installation5.1 Types of SLC DevicesThe following types of SLC devices can be used with the 5820 system. • *Model SD500-
SLC Device Installation150972 5-3When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must b
SLC Device Installation150972 5-55.5 Input Monitor Module (SD500-AIM) Wire and mount the SD500-AIM full-size input module as described in this section
SLC Device Installation150972 5-75.7 Relay Module InstallationThe information in this section applies to Model SD500-ARM Relay Modules. See Section 5.
150972 1-1Section 1IntroductionThe IntelliKnight 5820 Fire Alarm Control / Communicator is an analog addressable fire control system that meets the re
SLC Device Installation150972 5-95.8.2 Wiring the SD500-ANMNote: Installation and wiring of this device must be done in accordance with NFPA 72 and lo
SLC Device Installation150972 5-115.9 Duct Detector InstallationFigure 5-12 shows the layout of the SD505-ADH duct housing with a detector base in pla
SLC Device Installation150972 5-135.10.2 Dipswitch AddressingInput and relay module addresses are set using the dipswitch that appears on the module b
150972 6-1Section 6Programming OverviewThis section of the manual is intended to give you an overview of the programming process. Please read this sec
Programming Overview150972 6-33. Select for Program Menu.4. From the next menu, select for JumpStart.5. The message "WARNING Will reset all
Programming Overview150972 6-56.2.1 Input Point MappingInput points are assigned to input zones. Any input point can be assigned to any input zone. (I
Programming Overview150972 6-76.2.3 Zone Event Mapping There are 8 types of events that can occur in zones (see below). For each event type, you can a
Programming Overview150972 6-96.2.4 Mapping LED PointsFigure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typ
Programming Overview150972 6-113. Then press . The menus described in Section 7 of this manual will display. Section 6.5 of this manual is a quick r
Programming Overview150972 6-136.4.4 Editing KeysThe keys shown in Figure 6-9 are available for use when you are in the Program Menu.Figure 6-9 Editi
Introduction150972 1-31.3 Compatible ProductsThe chart below lists the products available from Silent Knight for use with the IntelliKnight 5820.Note:
Programming Overview150972 6-15Zone(cont.)Add Zone Adds next available zone number. Sec. 7.2.2Delete ZoneSelect Zone to be DeletedSec. 7.2.3View Zone
Programming Overview150972 6-17Point(Cont.)Internal Pwr and External PowerEnter Pt Input Point Type (detector/switch)Select Function Per JumpStartSele
Programming Overview150972 6-19System Option (cont.)Phone Lines Select Phone LineFor each phone line (1 & 2), select:Dialing Prefix Up to 9 digits
150972 7-1Section 7ProgrammingThis section of the manual manually program the IntelliKnight control panel. Each subsection discusses these menu option
Programming150972 7-35. Press to add a module.6. From the next screen, select the number that corresponds to the type of module you are adding from
Programming150972 7-5used with the IntelliKnight 5820.7.2.1.2 Edit Zone PropertiesZone properties consist of, alarm delay characteristics, heat detect
Programming150972 7-7Heat Detector SensitivityUse this feature to set the temperature that heat detectors will respond. The range is 135° to 150° F. A
Programming150972 7-9Example or Zone Mapping:Suppose you want to program Zone 1 so that:• Any alarm (detector, water flow or manual pull) would activa
Programming150972 7-117.2.2 Add ZoneTo add a zone, follow these steps:1. Enter the installer code.2. Press to display the installer menu.3. Select
Programming150972 7-137.3 GroupAn output group is made up of output points that have been programmed to respond in the same way. Output groups simplif
150972 2-1Section 2Agency Listings, Approvals, and Requirements2.1 Federal Communications Commission (FCC)1. The following information must be provide
Programming150972 7-15Silencing OptionsThe following silencing options are available for each output group.Response with System-Wide ConditionsYou can
Programming150972 7-177.3.4 View Group Points1. Enter the installer code.2. Press to display the installer menu.3. Select for Program Menu.Display
Programming150972 7-197.4 PointYou may need to change characteristics of individual input points (detectors and switches) even after using JumpStart.
Programming150972 7-21Internal and External 5815(Continued)SWITCH(Continued)PAS_ AC KPositive acknowledge switch. This switch must be used in zones pr
Programming150972 7-2313. Select the zone by pressing the or arrows.14. Press .15. Edit point name. See Section 7.4.3.1.OrPress to skip point na
Programming150972 7-257.4.3.1 Assigning a Name to a PointsYou can assign a name to a point to make it easier to recognize on a display.If you wish to
Programming150972 7-277.5.1.1 Edit Accounts6. From the next menu, select for Edit Account.A screen similar to one shown in Figure 7-11 will display.
Programming150972 7-29Fail AttemptsThis feature specifies the number of times the dialer should attempt to perform the dial/switch sequence before iss
Programming150972 7-316. Select the phone line to be edited (1 or 2) by pressing the or arrow, then press .Figure 7-12 Phone Lines Editing Screen
Programming150972 7-337.5.2.7 Answering Machine BypassThis option is used in conjunction with the IntelliKnight 5590 Downloading Software. This featur
150972 3-1Section 3Before You Begin InstallingThis section of the manual is intended to help you plan your tasks to facilitate a smooth installation.
Programming150972 7-356. Press for System Alarm Cadence. A screen similar to the one in Figure 7-14 will display. Select a cadence pattern for these
Programming150972 7-377.5.6 Miscellaneous OptionsThrough this programming option you can set the water flow delay time, low AC report delay, enable or
Programming150972 7-397.5.6.5 Change AC Line FrequencyThe panel’s AC frequency is selectable for 50, 60 Hz, or Neither. AC Frequency feature dictates
Programming150972 7-417.6 JumpStart AutoprogrammingTo run JumpStart:1. Enter the installer code.2. Press to display the installer menu.3. Select f
Programming150972 7-437.8 Access CodesYou can edit the default User and Installer codes through this programming option.To change a access code:1. Ent
150972 8-1Section 8System OperationOperation of the IntelliKnight 5820 is simple. Menus guide you step-by-step through operations. This section of the
System Operation150972 8-38.3.1 User MenuThe User Menu is actually a set of menus for basic system operation. It allows you to perform such operations
System Operation150972 8-58.4.4 Conduct a Fire Drill1. From the User or Installer Menu, press for System Tests.2. Press for Fire Drill. You will b
System Operation150972 8-78.4.9 Reset alarmsPress and enter your code or rotate the key at the prompt. If an external reset switch has been installe
System Operation150972 8-98.4.16 Communicating with a Remote ComputerAn installer at the panel site can initiate communications between the panel and
Before You Begin Installing150972 3-33.4 Wiring SpecificationsInduced noise (transfer of electrical energy from one wire to another) can interfere wit
System Operation150972 8-118.5 Operation Mode BehaviorThe IntelliKnight 5820 panel can be in one of seven conditions at any given moment: Normal, Alar
System Operation150972 8-13Prealarm A single detector trips in a 2-Count zone. (2-Count means two detectors must trip before an alarm is reported.)Tou
150972 9-1Section 9ReportingThis section lists receivers that are compatible with the 5820 and reporting codes sent for SIA and Contact ID formats.9.1
Reporting150972 9-3Printer paper restored. Trouble 3 335 Exp ID 000Printer offline. Trouble 1 336 Exp ID 000Printer back online. Trouble 3 336 Exp ID
Reporting150972 9-5Zone-based AUX 1 switch input has been re-enabled.Disable 3 571 Exp ID Pnt #Zone-based AUX 2 switch input has been re-enabled.Disab
Reporting150972 9-7Manual pull switch trouble Trouble FT ZoneDetector trouble Trouble FT ZonePositive Alarm Sequence acknowledge switch trouble Troubl
Reporting150972 9-9Printer offline. Trouble VZAn unexpected SLC device has been detected. Trouble pi Exp. ID XE Pnt #An unexpected SLC device has been
150972 10-1Section 10Testing and Troubleshooting10.1 TroubleshootingThis section of the manual offers suggestions for troubleshooting hardware problem
Testing and Troubleshooting150972 10-310.3 Built-in Troubleshooting and Testing ToolsThe IntelliKnight fire control panel has several built-in testing
Testing and Troubleshooting150972 10-510.3.3 I/O Point ControlThis feature allows you to toggle any output on or off and trip any input device. This c
150972 3-53.5 Board Assembly DiagramFigure 3-2 Model 5820 AssemblyFigure 3-2 shows the circuit boards, metal housing and annunciator that attach the
150972 11-1Section 11Installation RecordsThis section of the manual is for you to use if you wish to track of how points, zones, and groups have been
Installation Records150972 11-35815-1 1 5815-1 425815-1 2 5815-1 435815-1 3 5815-1 445815-1 4 5815-1 455815-1 5 5815-1 465815-1 6 5815-1 475815-1 7 58
Installation Records150972 11-55815-2 35 5815-2 755815-2 36 5815-2 765815-2 37 5815-2 775815-2 38 5815-2 785815-2 39 5815-2 795815-2 40 5815-2 805815-
150972 A-1Appendix ACompatible DevicesA.1 Two-Wire Smoke DetectorsThe table below lists two-wire smoke detectors that are compatible with the IntelliK
Compatible Devices150972 A-3A.3 Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on
Compatible Devices150972 A-5System SensorSS2415ADA StrobeSystem SensorSS2475ADA StrobeSystem SensorPS2415ADA Mini-Horn/StrobeSystem SensorPS241575ADA
Compatible Devices150972 A-7WheelockLSM-24-VFR Remote StrobeWheelockLS1M-24-VFR Remote StrobeWheelockLS3M-24-VFR Remote StrobeWheelockLSPM-24-VFR R
150972 B-1Appendix BWord and Special Characters ListsThis section contains tables of programmable words or special characters that may be used for dev
150972Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight after Sep